Quick Start Guide
Step 4: Pull the cable through cable gland/conduit
Step 5: Connect the cable wires
See the wiring diagrams on page 15 to 18.
Step 6: Ensure proper grounding
Make sure grounding is done (including IS ground inside Terminal compartment)
according to Hazardous Locations Certifications, national and local electrical
codes.
Transmitter housing grounding
The most effective transmitter housing grounding method is a direct connection
to earth ground with minimal (< 1 ) impedance.
There are two grounding screw connections provided (see Figure 1).
Figure 1. Ground Screws
A. Internal ground screw
B. External ground screw
Adapters are required if M20 glands are used.