Transmitter Um = 250V
Thermal data:
Ambient temperature
(°C) Process temperature (°C) T-Class sensor
–50 to +70 –50 to +75 T6
–50 to +70 –50 to +95 T5
–50 to +70 –50 to +130 T4
–50 to +70 –50 to +195 T3
–50 to +70 –50 to +250 T2
Remote mounted sensor: in type of protection Ex ia IIC, only to be
connected to the associated Model 8600D Vortex Flow meter
electronics.
The maximum allowable length of the interconnecting cable is 152 m
(500-ft.)
Special conditions for safe use (X):
1. For information regarding the dimensions of the
flameproof joints, the manufacturer shall be contacted.
2. The Flowmeter is provided with special fasteners of
property class A2-70 or A4-70.
3. Units marked with “Warning: Electrostatic Charging
Hazard” may use non- conductive paint thicker than 0.2
mm. Precautions shall be taken to avoid ignition due to
electrostatic charge of the enclosure.
4. When the equipment is installed, precautions shall be
taken to ensure the ambient temperature of the
transmitter lies between –50 °C to +70 °C, taking into
account process fluid effects. If the ambient temperature is
outside this range remote transmitters shall be used.
Combined ATEX certifications
K1
Combination of E1, I1, N1, and ND
8.5 EurAsian Conformity (EAC)
This section addresses compliance with the requirements of technical
regulations of the Customs Union.
• TR CU 020/2011—Electromagnetic compatibility of technical means
• TR CU 032/2013—On the safety of equipment operating under excessive
pressure