EasyManua.ls Logo

Emerson Rosemount 8732E - Page 30

Emerson Rosemount 8732E
38 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Quick Installation Guide
00825-0100-4662, Rev CC
December 2012
Rosemount 8732
30
North American Certifications
Factory Mutual (FM)
N0 Non-incendive for Class I, Division 2
Groups A, B, C, and D non-flammable fluids
(T4 at 60 °C: -50 °C Ta +60 °C)
Dust-ignition proof Class II/III, Division 1
Groups E, F, and G (T5 at 60 °C)
Hazardous Locations; Enclosure Type 4X
N5 Non-incendive for Class I, Division 2,
Groups A, B, C, and D flammable fluids
(T4 at 60 °C: -50 °C Ta +60 °C)
Dust-ignition proof Class II/III, Division 1
Groups E, F, and G (T5 at 60 °C)
Hazardous Locations; Enclosure Type 4X
Requires sensors with N5 Approval
E5 Explosion proof for Class I, Division 1
Groups C and D (T6 at 60 °C)
Dust-ignition proof Class II/III, Division 1
Groups E, F, and G (T5 at 60 °C),
Non-incendive for Class I, Division 2
Groups A, B, C, and D flammable fluids
(T4 at 60 °C: -50 °C Ta +60 °C)
Hazardous Locations; Enclosure Type 4X
Canadian Standards Association (CSA)
N0 Non-incendive for Class I, Division 2
Groups A, B, C, and D non-flammable fluids
(T4 at 60 °C: -50 °C Ta +60 °C)
Dust-ignition proof Class II/III, Division 1
Groups E, F, and G (T4 at 60 °C)
Hazardous Locations; Enclosure Type 4X
European Certifications
E1 ATEX Flameproof
Certificate No: KEMA 07ATEX0073 X
II 2G Ex de IIC T6 or
II 2G Ex de [ia] IIC T6
without LOI (-50 °C Ta +60 °C)
with LOI (-20 °C Ta +60 °C)
V
max
= 250 V AC or 42 V DC
0575
4662RevCCQIG.fm Page 30 Thursday, January 10, 2013 5:11 PM