Unidrive M700/M701 / Unidrive HS70/HS71 Control Getting Started Guide 37
Issue Number: 2
Safety information Introduction Control connections Getting started
Basic parameters
(Menu 0)
Running the motor
Further information
6.2.2 RFC-A mode (with position feedback)
Induction motor with position feedback
For simplicity only an incremental quadrature encoder will be considered here. For information on
setting up one of the other supported speed feedback devices, refer to Setting up a feedback device
in the Drive User Guide.
Action Detail
Before
power-up
Ensure:
Drive Enable signal is not given (terminal 31)
Run signal is not given
Motor and feedback device are connected
Power-up
the drive
Verify that RFC-A mode is displayed as the drive powers up. If the
mode is incorrect see section 4.7 Changing the operating mode on
page 20.
Ensure: Drive displays ‘Inhibit
Set motor
feedback
parameters
Incremental encoder basic set-up
Enter:
Drive encoder type in Pr 03.038 = AB (0): Quadrature encoder
Encoder power supply in Pr. 03.036 = 5 V (0), 8 V (1) or 15 V (2).
Drive encoder Lines Per Revolution (LPR) in Pr 03.034
Drive encoder termination resistor setting in Pr 03.039:
0 = A-A\, B-B\, Z-Z\ termination resistors disabled
1 = A-A\, B-B\, termination resistors enabled, Z-Z\ termination
resistors disabled
2 = A-A\, B-B\, Z-Z\ termination resistors enabled
Motor
thermistor
set-up
If a thermistor is connected to terminal 8, then the Analog Input 3 Mode
(07.015) parameter must be set to Thermistor Short Cct (7), Thermistor
(8) or Therm No Trip (9).
Enter motor
nameplate
details
Motor rated frequency in Pr 00.047 (Hz)
Motor rated current in Pr 00.046 (A)
Motor rated speed in Pr 00.045 (rpm)
Motor rated voltage in Pr 00.044 (V) - check if or connection
Set max
speed
Enter:
Maximum speed in Pr 00.002 (rpm)
Set accel /
decel rates
Enter:
Acceleration rate in Pr 00.003 (s/1000 rpm)
Deceleration rate in Pr 00.004 (s/1000 rpm) (If braking resistor
installed, set Pr 00.015 = FAST. Also ensure Pr 10.030, Pr 10.031
and Pr 10.061 are set correctly, otherwise premature ‘Brake R Too
Hot’ trips may be seen).
If output voltage from the encoder is >5 V, then the
termination resistors must be disabled Pr 03.039 to 0.
NOTE
Setting the encoder voltage supply too high for the encoder
could result in damage to the feedback device.
CAUT ION
The thermistor input will be disabled until Pr 07.015 is set to
one of the above.
NOTE
Mot X XXXXXXXXX
No XXXXXXXXXX kg
IP55 I.cl F C 40 s S1
°
VHzmin
-1
kW cos
φ
A
230
400
50 1445 2.20 0.80 8.50
4.90
CN = 14.5Nm
240
415
50 1445 2.20 0.76 8.50
4.90
CN = 14.4Nm
CTP- VEN 1PHASE 1=0,46A P=110W R.F 32MN
I.E.C 34 1( 87)
0.02
t
1000rpm
0.03
t
0.04
Unidrive M700_M701 Getting Started Guide English iss7.book Page 37 Friday, December 12, 2014 1:14 PM