44 SI-Ethernet User Guide
Issue: 1
Controls and displays the subnet mask of the module.
If DHCP is enabled this parameter becomes read-only, and until a subnet mask is
allocated to the module will display 0.0.0.0.
If DHCP is disabled the module will initialize, on reset or power cycle, with the subnet
mask stored for the parameter.
Controls and displays the default gateway of the module.
If DHCP is enabled this parameter becomes read-only, and until a default gateway is
allocated to the module will display 0.0.0.0.
If DHCP is disabled the module will initialize, on reset or power cycle, with the default
gateway stored for the parameter.
S.02.007 Subnet Mask
Minimum
0
(Display: 0.0.0.0)
Maximum
4294967295
(Display:255.255.255.255)
Default
4294967040
(Display:255.255.255.0)
Units
Type 32 Bit User Save Update Rate
DHCP enabled:
write on event;
DHCP disabled:
read on reset
Display Format IP Address Decimal Places 0
Coding RW, BU
S.02.008 Default Gateway
Minimum
0
(Display: 0.0.0.0)
Maximum
4294967295
(Display:255.255.255.255)
Default
3232236030
(Display:192.168.1.254)
Units
Type 32 Bit User Save Update Rate
DHCP enabled:
write on event;
DHCP disabled:
read on reset
Display Format IP Address Decimal Places 0
Coding RW, BU