SI-Ethernet User Guide 177
Issue: 1
Safety
information
Introduction
Mechanical
installation
Electrical
installation
Getting started Parameters
Key features
and Protocols
PC Applications Security Diagnostics
Glossary of
terms
Index
SpeedRef
Sets or returns the speed reference in RPM.
Closed loop
Get/Set SpeedRef = Pr 0.01.021 (Scaled to 0 decimal places).
Open loop
Get SpeedRef = (Pr 0.01.021 * 60) / Pole Pairs (Scaled to 0 decimal places).
Set Pr 0.01.021 = (SpeedRef * Pole Pairs) / 60 (Scaled to 0 decimal places).
TorqueActual
Returns the actual load on the motor as a percentage of the rated motor load. This
attribute has 1 decimal place precision, a value of 1000 represents 100.0 % load.
Get Pr 0.04.020 (Scaled to 1 decimal place).
TorqueRef
Sets the load (torque) reference as % of rated motor load (torque). This attribute has 1
decimal place precision, so a value of 1000 represents 100.0 % load.
Set Pr 0.04.008 = TorqueRef / 10 (Scaled to 1 decimal place).
Get TorqueRef = Pr 0.04.008 * 10 (Scaled to 1 decimal place).
RefFromNet
Indicates the source of the speed reference.
TRUE if Pr 0.01.049 = 3 and Pr 0.01.050 = 1.
FALSE otherwise.
Name: SpeedRef
Class 0x2A Default N/A
Instance 0x01 Data Type USINT
Attribute 0x08 Access Get/Set
Name: TorqueActual
Class 0x2A Default N/A
Instance 0x01 Data Type USINT
Attribute 0x0B Access Get
Name:
Class 0x2A Default N/A
Instance 0x01 Data Type USINT
Attribute 0x0C Access Get/Set
Name: RefFromNet
Class 0x2A Default
Instance 0x01 Data Type USINT
Attribute 0x1D Access Get