184 SI-Ethernet User Guide
Issue: 1
Table 10.2 Drive trip indications
10.3 Ethernet sub trip codes
Table 10.3 below shows the possible Ethernet sub trip codes displayed in Pr 0.10.070
and their relevant text strings.
Table 10.3 Ethernet error codes
Trip Description
SlotX HF
The drive has detected that an Ethernet interface is present but is unable to
communicate with it due to a hardware fault.
SlotX Error User trip generated by the Ethernet interface
SlotX Not Fitted
This trip will occur if a drive slot was previously configured with an option
module but on power up, no option module was detected.
SlotX Different
This trip will occur if a drive slot was previously configured with an option
module but on power up, a different option module was detected. Replacing
the option module with another one of the same ID number will not initiate
this trip. The trip will also occur if an option module is installed to a
previously unused slot.
Value
Pr 0.10.070
Sub trip string Description
100 Link Loss Network link has been lost
101 E/IP Timeout An Ethernet/IP RPI timeout trip has occurred
102 E/IP Read Param
Invalid read consistency parameter, is parameter read
only?
103 E/IP Write Param
Invalid write consistency parameter, is parameter read
only?
104 E/IP Fault An unexpected Ethernet/IP error has occurred
105 Modbus Timeout The Modbus connection has timed out
106 Cyclic Timeout Cyclic Rx link timeout
107 Cyclic RX Late Cyclic Rx data was received late
108 INIT Switch Ethernet switch initialization error
109 INIT PTP IEEE1588 (Precision Time Protocol) initialization error
110 INIT Cyclic Cyclic data initialization error
111 INIT Modbus Modbus TCP initialization error
112 INIT SMTP Email (SMTP) initialization error
113 INIT Ethernet/IP Ethernet/IP initialization error
114 INIT TCP/IP TCP/IP initialization error
115 Ethernet Failure Ethernet controller initialization error
116 E/IP PLC IDLE Ethernet/IP PLC Idle
117 Sync Task ORun Synchronous task overrun