Document Part # 026-4280 Rev 1 Page 18 of 33
©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use.
Visit our website at www.climate.emerson.com for the latest technical documentation and updates.
13 Parameter List
Parameter Description
REGULATION
rtC Access to CLOCK submenu (if present)
Set Temperature setpoint (LS to US)
Hy
Differential: (0,1 to 25, 5°C; 1 to 45°F): Intervention differential for setpoint, always positive. Solenoid
valve Cut IN is Setpoint Plus Differential (Hy). Solenoid valve Cut OUT is when the temperature reaches
the setpoint.
LS
Minimum setpoint limit: (-55.0°C to SET; -67°F to SET) Sets the minimum acceptable value for the
setpoint.
US
Maximum setpoint limit: (SET to 150°C; SET to 302°F) Set the maximum acceptable value for
setpoint.
OdS
Outputs activation delay at start up: (0 to 255 minutes) This function is enabled at the initial start up
of the instrument and inhibits any output activation for the period of time set in the parameter.
(AUX and Light can work)
AC
Anti-short cycle delay: (0 to 60 minutes) interval between the solenoid valve stop and the following
restart.
CCt
Compressor ON time during continuous cycle: (0.0 to 24.0 hours; resolution 10 minutes) Allows to
set the length of the continuous cycle: compressor stays on without interruption for the CCt time. Can
be used, for instance, when the room is filled with new products.
CCS
Setpoint for continuous cycle: (-55 to 150°C / -67 to 302°F) it sets the setpoint used during the
continuous cycle.
Con
Solenoid valve ON time with faulty probe: (0 to 255 minutes) time during which the solenoid valve
is active in case of faulty thermostat probe. With COn = 0 solenoid valve is always OFF.
CoF
Solenoid valve OFF time with faulty probe: (0 to 255 minutes) time during which the solenoid valve
is off in case of faulty thermostat probe. With COF = 0 solenoid valve is always active.
DISPLAY
CF
Temperature measurement unit: °C = Celsius; °F = Fahrenheit.
WARNING: When the measurement unit is changed the parameters with temperature values have to be
checked.
rES Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display.
Lod
Instrument display: (nP; P1; P2, P3, P4, P5, P6, tEr, dEF) it selects which probe is displayed by the
instrument. P1, P2, P3, P4, P5, P6, tEr = virtual probe for thermostat, dEF = virtual probe for defrost.
rEd
Remote display: (nP; P1; P2, P3, P4, P5, P6, tEr, dEF) it selects which probe is displayed by the X-REP.
P1, P2, P3, P4, P5, P6, tEr= virtual probe for thermostat, dEF= virtual probe for defrost.
dLy
Display delay: (0 to 24.0 minutes; resolution 10 seconds) when the temperature increases, the
display is updated of 1 °C/1°F after this time.
rPA
Regulation probe A: (nP; P1; P2, P3, P4, P6) first probe used to regulate room temperature. If rPA=nP
the regulation is performed with real value of rPb.
rPb
Regulation probe B: (nP; P1; P2, P3, P4, P5) second probe used to regulate room temperature.
If rPb=nP the regulation is performed with real value of rPA.
rP3
Regulation probe 3: (nP; P1; P2, P3, P4, P6) third probe used to regulate room temperature, with
rPd = rAb, Aur, LoE, HiE.
rP4
Regulation probe 4: (nP; P1; P2, P3, P4, P6) fourth probe used to regulate room temperature, with
rPd = rAb, Aur, LoE, HiE.
Table 13-1 - Parameter List