Document Part # 026-4280 Rev 1 Page 29 of 33
©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use.
Visit our website at www.climate.emerson.com for the latest technical documentation and updates.
17 Default Setting Values
Relay Outputs (Total current on loads MAX 16A)
Solenoid Valve: relay SPST 5(3) A, 250Vac
Defrost: relay SPST 16A, 250Vac
Fan: relay SPST 8A, 250Vac
Light: relay SPST 16A, 250Vac
Alarm (XM670K): SPDT relay 8A, 250Vac
Aux (XM670K): SPST relay 8A, 250Vac
Optional Output (AnOUT)
Depending on the model
PWM/ Open Collector outputs: PWM or 12VDC max 40mA
Analog Output: 4 to 20mA or 0 to 10V
Purpose of Control Operating Control
Construction of Control
Incorporated control, intended to be used in Class I or Class II equipment.
Label M1 M2 M3 M4 Menu Parameters Description
rtc --- Pr1 Access by RTC submenu
SEC LOC --- LAN mode selection: Local or Global
SEt 2.0 2.0 -18.0 -18.0 --- Setpoint
Hy 2.0 2.0 2.0 2.0 Pr1 Differential
LS -30 -30 -30 -30 Pr2 Minimum setpoint
US 10 10 10 10 Pr2 Maximum setpoint
odS 1 Pr2 Outputs activation delay at start up
AC 0 Pr2 Anti-short cycle delay
CCt 0.0 Pr2 Continuous cycle duration
CCS 2.0 Pr2 Continuous cycle setpoint
Con 5 Pr2 Compressor ON time with faulty probe
CoF 10 Pr2 Compressor OFF time with faulty probe
CF °C Pr2 Measurement unit: Celsius, Fahrenheit
rES dE Pr2 Resolution (only C): decimal, integer
Lod P1 Pr2 Local display: default display
rEd P1 Pr1 Remote display: default display
dLy 0 Pr1 Display delay
rPA P1 Pr1 Regulation probe A
rPb nP Pr1 Regulation probe B
rP3 nP Pr2 Regulation probe 3
rP4 nP Pr2 Regulation probe 4
rPd rPA Pr2 Temperature Regulation Strategy
rPE 100 Pr2 Virtual probe percentage (rPd = rAb)
dPA Pr2 Pr2 Defrost probe A
dPb nP Pr2 Defrost probe B
tdF EL EL EL EL Pr2 Kind of defrost: air, resistors, inversion
Table 17-1 - Default Setting Values
Table 16-1- XM670K Technical Specifications