Document Part # 026-4280 Rev 1 Page 30 of 33
©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use.
Visit our website at www.climate.emerson.com for the latest technical documentation and updates.
EdF in Pr2 Defrost mode: Clock or interval
Srt 150 Pr2 Differential for heater
Hyr 2.0 Pr2 Time out for heater (if temp > Srt)
tod 255 Pr2 Defrost with two probes
d2P n n n n Pr2 Defrost with two probes
dtE 8.0 8.0 8.0 8.0 Pr1 First defrost termination temperature
dtS 8.0 8.0 8.0 8.0 Pr2 Second defrost termination temperature
idF 6 6 6 6 Pr1 Interval between defrosts
idE y Pr2 Storage in EEPROM defrost interval
ndt 3 3 3 3 Pr2 Minimum Defrost Time
MdF 30 30 30 30 Pr2 Maximum defrost duration
dSd 0 Pr2 Delay for defrost on call
dFd it Pr2 Visualization during defrost
dAd 30 Pr2 Visualization delay for temperature after defrost
Fdt 0 0 2 2 Pr2 Dripping time
dPo n Pr2 Defrost at power ON
dAF 0 Pr2 Delay defrost after freezing
Pdt F-C Pr2 Pump down type
Pdn 0 Pr2 Pump down duration
Ctd 6 6 6 6 Pr2 Differential for defrost start
nbd 4.0 4.0 4.0 4.0 Pr2 Minimum Compressor run time before defrost
Mdb 16.0 16.0 16.0 16.0 Pr2 Maximum Compressor run time before defrost
nct -30 -30 -30 -30 Pr2 Minimum coil temperature to trigger a defrost
FAP P2 Pr2 Fan probe
FnC O-y o-y o-n o-n Pr1 Fan operating mode
Fnd 0 0 5 5 Pr1 Fan delay after defrost
FCt 10 Pr2 Temperature differential to avoid short cycles of fans
FSt 15.0 15.0 2.0 2.0 Pr1 Fan stop temperature
FHy 1.0 Pr2 Fan stop hysteresis
tFE n Pr2 Fan regulation by temperature in defrost
Fod 0 Pr2 Fan activation time after defrost (without compressor)
Fon 0 Pr2 Fan ON time
FoF 0 Pr2 Fan OFF time
trA UAL Pr2 Kind of regulation with PWM output
SOA 0 Pr2 Fixed speed for fan
SdP 30.0 Pr2 Default Dewpoint value
ASr 1.0 Pr2 Differential for fan / offset for anti-sweat heater
PbA 5.0 Pr2 Proportional band for modulating output
AMi 0 Pr2 Minimum output for modulating output
AMA 100 Pr2 Maximum output for modulating output
Label M1 M2 M3 M4 Menu Parameters Description
Table 17-1 - Default Setting Values