Auxiliary Output Parameters List • 17
i1F
Digital input 1 function: (EAL - bAL - PAL - dor - dEF - AUS - LiG - OnF - Htr - FHU - ES - Hdy) EAL=
external alarm; bAL= serious external alarm; PAL= pressure switch activation; dor= door open; dEF= defrost
activation; AUS= auxiliary activation; LiG= light activation; OnF= switch on/off the device; Htr= change
type of action; FHU= not used; ES= activate energy saving; Hdy= activate holiday function
d1d
Time interval/delay for digital input alarm: (0 to 255 min.) Time interval to calculate the number of the
pressure switch activation when i1F=PAL. If I1F=EAL or bAL (external alarms), “d1d” parameter defines
the time delay between the detection and the successive signaling of the alarm. If i1F=dor this is the delay to
activate door open alarm.
i2P
Digital input 2 polarity: (cL - oP) CL: the digital input is activated by closing the contact; OP: the digital input
is activated by opening the contact.
i2F
Digital input 2 function: (EAL - bAL - PAL - dor - dEF - AUS - LiG - OnF - Htr - FHU - ES - Hdy) EAL=
external alarm; bAL= serious external alarm; PAL= pressure switch activation; dor= door open; dEF= defrost
activation; AUS= auxiliary activation; LiG= light activation; OnF= switch on/off the device; Htr= change
type of action; FHU= not used; ES= activate energy saving; Hdy= activate holiday function
d2d
Time interval/delay for digital input alarm: (0 to 255 min.) Time interval to calculate the number of the
pressure switch activation when i2F=PAL. If I2F=EAL or bAL (external alarms), “d2d”parameter defines the
time delay between the detection and the successive signaling of the alarm. If i2F=dor this is the delay to
activate door open alarm.
i3P
Digital input 3 polarity: (cL - oP) CL: the digital input is activated by closing the contact; OP: the digital input
is activated by opening the contact.
i3F
Digital input 3 function: (EAL - bAL - PAL - dor - dEF - AUS - LiG - OnF - Htr - FHU - ES - Hdy) EAL=
external alarm; bAL= serious external alarm; PAL= pressure switch activation; dor= door open; dEF= defrost
activation; AUS= auxiliary activation; LiG= light activation; OnF= switch on/off the device; Htr= change
type of action; FHU= not used; ES= activate energy saving; Hdy= activate holiday function
d3d
Time interval/delay for digital input alarm: (0 to 255 min.) Time interval to calculate the number of the
pressure switch activation when i3F=PAL. If i3F=EAL or bAL (external alarms), “d3d” parameter defines
the time delay between the detection and the successive signaling of the alarm. If i3F=dor this is the delay to
activate door open alarm.
nPS
Pressure switch number: (0 to 15) Number of activation of the pressure switch, during the “d#d” interval,
before signaling the alarm event (I2F= PAL). If the nPS activation in the did time is reached, switch off and
on the device to restart normal regulation.
odc
Compressor and fan status when open door: no = normal; Fan = Fan OFF; CPr = Compressor OFF; F_C =
Compressor and fan OFF.
rrd Outputs restart after door open alarm.
ENERGY SAVING
ESP Energy saving probe selection: (nP - P1 - P2 - P3 - P4 - P5 - tEr).
HES
Temperature increase during the Energy Saving cycle: (-54 to 54°F / -30 to 30°C) sets the increasing value
of the setpoint during the Energy Saving cycle.
PEL
Energy saving activation when light is switched off: (n to Y) n= function disabled; Y= energy saving is
activated when the light is switched off and vice versa.
LAN MANAGEMENT
LMd
Defrost synchronization: y= the section send a command to start defrost to other controllers, n= the section
don't send a global defrost command
Table 8-1 - XM670 to XM679 Parameters List