26 • XM679K I&O Manual 026-1218 Rev 4
14.1.EE Alarm
The controllers are provided with an internal check
for data integrity. Alarm EE flashes when a failure in
the memory data occurs. In such cases, the alarm
output is enabled.
14.2.Alarm Recovery
Probe alarms, P1 (probe1 faulty), P2, P3, P4, P5, and
P6 automatically stop 10 seconds after the probe
restarts normal operation. Check connections before
replacing the probe. Temperature alarms, HA, LA,
HAd, LAd, HAF, and LAF automatically stop as
soon as the thermostat temperature returns to normal
values or when the defrost starts. External alarms
EAL and bAL stop as soon as the external digital
input is disabled.