Third situation:
If Temperature(NOTE1) is higher than ALARM SET VALUES ABSOLUTE MAX plus
ALARM SET VALUES DIFFERENTIAL for more than a minute ALARM STATUS 1 DIFFERENTIAL alarm
is switched ON.
ON
OFF
Process Value [°C]
(NOTE1)
Settemp
(NOTE2)
DIFFERENTIAL
ALARM
SET VENTILATION PAGE
VENTILATION8
ALARM SET VALUES
DIFFERENTIAL
ALARM SET VALUES
DIFFERENTIAL
Outside temp.
(Outside temp.>ALARM SET VALUES ABSOLUTE MAX)
ALARM SET VALUES
ABSOLUTE MAX
19.07.06 14:30:21
HOUSE 20.2°C
OUT 12.1°C
HUMIDITY 65%
DAY -5
(Outside temp.>Temperature (NOTE1) + SET VENTILATION PAGE VENTILATION8)
NOTE1:
If VENTIL. PARAMETERS PAGE SENSOR parameter is ROOM1;
Temperature = ROOM1 sensor’s temperature,
If VENTIL. PARAMETERS PAGE SENSOR parameter is ROOM2;
Temperature = ROOM2 sensor’s temperature,
If VENTIL. PARAMETERS PAGE SENSOR parameter is ROOM1&2;
Temperature =( ROOM1 sensor’s temperature + ROOM2 sensor’s temperature) / 2.
NOTE2:
If curve is enabled;
Settemp= HOUSE TEMP from curve.
Min.Vent= MIN. VENT from curve.
Max.Vent=MAX. VENT from curve.
If curve is disabled;
Settemp= SET VALUES PAGE TEMP.HOUSE.
Min.Vent= SET VALUES PAGE VENT. MIN.
Max.Vent= SET VALUES PAGE VENT. MAX.
4. ALARM1 alarm
If ALARM1 input is ON then ALARM STATUS 1 alarm is switched ON.
5. NEGATIVE PRESSURE alarm
As long as INFLUENCE 2 PAGE NEG PRESSURE parameter is different from NON, negative pressure input
is enabled. Otherwise negative pressure input is disabled.
Negative pressure
alarm is ON
INFLUENCE 2 PAGE
NEG.PRE.TOFF
INFLUENCE 2 PAGE
NEG.PRE.TON
ON
OFF
ON
OFF
Time[sec]
Time[sec]
NEG
PRESSURE
INPUT
NEG
PRESSURE
ALARM
31
6. HUMIDITY alarm
If HUMIDITY sensor is broken while EPC is working then ALARM STATUS 1 HUMIDITY alarm is switched
ON.
Fourth situation:
If Temperature(NOTE1) is lower than Settemp(NOTE2) minus ALARM SET VALUES DIFFERENTIAL
for more than a minute ALARM STATUS 1 DIFFERENTIAL alarm is switched ON.