EMKO EPC-3 - Curve Function Graphics: Humidity and Ventilation; Humidity Curve Graphics; Ventilation Curve Graphics

EMKO EPC-3
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
70
Day
Humidity[%]
(NOTE1)
Step1 Day=1
Step2 Day=8
Step3 Day=10
Step4 Day=14
Step5 Day=20
Step6 Day=30
Step7 Day=32
Step8 Day=36
Step9 Day=38
Step10 Day=40
80
76
Day=12
73
12. day is between Step3 and Step4. So 12. day; humidity(NOTE1) is 73%
3%00
Max.Vent
(NOTE1)
Step1 Day=1
Step2 Day=8
Step3 Day=10
Step4 Day=14
Step5 Day=20
Step6 Day=30
Step7 Day=32
Step8 Day=36
Step9 Day=38
Step10 Day=40
5%00
Day=12
4%00
12. day is between Step3 and Step4. So 12. day; Max.Vent(NOTE1) is 4%00
0%20
Min.Vent
(NOTE1)
Step1 Day=1
Step2 Day=8
Step3 Day=10
Step4 Day=14
Step5 Day=20
Step6 Day=30
Step7 Day=32
Step8 Day=36
Step9 Day=38
Step10 Day=40
0%40
Day=12
0%30
12. day is between Step3 and Step4. So 12. day; Min.Vent(NOTE1) is 0%30
NOTE1:
If working with curve;
Humidity= HUMIDITY from curve + HUMIDITY PARAMETERS PAGE OFFSET.
Min.Vent= MIN. VENT from curve.
Max.Vent=MAX. VENT from curve.
If Curve is disable;
Humidity= SET VALUES PAGE HUMIDITY + HUMIDITY PARAMETERS PAGE OFFSET.
Min.Vent= SET VALUES PAGE VENT. MIN.
Max.Vent= SET VALUES PAGE VENT. MAX.
Day=-5
Day=-5
Day=999
Day=-5
Day
Day=999
Day
Day=999