6.4.6.4 VENTILATION FUNCTION(BASIC&TUNNEL)
2. Fan Analog ventilation control:
Fan analog ventilation control
simultaneously works
with fan linear ventilation control.
(BASIC&TUNNEL VENT)
If SET VENTILATION PAGE FAN ANALOG
parameter is TUNNEL
House [°C]
Fans
Analog
Output[V]
10.0
C.HYS
0.0
F.HYS
F.HYS
F.HYS
F.HYS
F.HYS
If SET VENTILATION PAGE FAN ANALOG
parameter is BASIC&TUN. and
SET VENTILATION PAGE BASIC VENT:ON/OFF
House [°C]
Fans
Analog
Output[V]
10.0
0.0
1.25
2.50
3.75
5.00
6.25
7.50
8.75
1.66
3.32
5.00
6.66
8.32
If SET VENTILATION PAGE FAN ANALOG
parameter is BASIC&TUN. and
SET VENTILATION PAGE BASIC VENT
:PROPORTION
House [°C]
Fans
Analog
Output[V]
10.0
0.0
1.25
2.50
3.75
5.00
6.25
7.50
8.75
Settemp
(NOTE1)
A (NOTE2)
B (NOTE2)
C (NOTE2)
D (NOTE2)
E (NOTE2)
F (NOTE2)
G (NOTE2)
H (NOTE2)
MIN.VENT
MIN.VENT
NOTE1:
If curve is enabled;
Settemp= HOUSE TEMP from curve,
Min.Vent= MIN. VENT from curve,
Max.Vent=MAX. VENT from curve.
If curve is disabled;
Settemp= SET VALUES PAGE TEMP.HOUSE,
Min.Vent= SET VALUES PAGE VENT. MIN,
Max.Vent= SET VALUES PAGE VENT. MAX.
NOTE2:
A = Settemp(NOTE1) + SET VENTILATION PAGE VENT1.
B = Settemp(NOTE1) + SET VENTILATION PAGE VENT2.
C = Settemp(NOTE1) + SET VENTILATION PAGE VENT3.
D = Settemp(NOTE1) + SET VENTILATION PAGE VENT4.
E = Settemp(NOTE1) + SET VENTILATION PAGE VENT5.
F = Settemp(NOTE1) + SET VENTILATION PAGE VENT6.
G = Settemp(NOTE1) + SET VENTILATION PAGE VENT7.
H = Settemp(NOTE1) + SET VENTILATION PAGE VENT8.
60