If no operation is performed in Programming mode for 20 seconds, device turns to
main operation screen automatically.
Low Reading Adjustment Value Parameter ( Default = -1999 )
It defines minimum value for dual point reading adjustment
ýt can be adjusted -1999 to ( -1)
Up Reading Adjustment Value Parameter( Default = 9999 )
It defines maximum value for dual point reading adjustment
ýt can be adjusted ( +1) to 9999
ReadingAdjustment Selection Parameter ( Default = 0)
It defines which reading adjustment type is active. It can be adjusted from 0 to 1
Selectedprocessinputtypeisreadaccordingtothestandard
readingadjustment.
Selectedprocessinputtypeisreadaccordingtotheuserreading
adjustment.
User Reading Adjustment Low Limit Analogue Value Parameter
Please refer to section 6.
In this parameter, the equivalent voltage or current for low reading adjustment
value parameter is determined.( )
User Reading Adjustment Up Limit Analogue Value Parameter
Please refer to section 6.
In this parameter, the equivalent voltage or current for up reading adjustment
value parameter is determined. ( )
and parameters are observed if reading adjustment selection parameter
= 1, otherwise these parameters are can not be observed.
Alarm Hysteresis Parameter ( Default = 0)
Alarm hysteresis value.
It can be adjusted from 0 to ( - ) / 2
Alarm Type Selection Parameter ( Default = 1)
ProsesHigh Alarm
ProsesLow Alarm
Alarm On Delay Time Parameter ( Default = 0)
It can be adjusted from 0 to 99 minutes.
Alarm Off Delay Time Parameter ( Default = 0)
It can be adjusted from 0 to 99 minutes.
When this parameter is 99, if increment button is pressed, is observed
and alarm latching output is selected. To make the alarm latching output
passive, decrement button must be pressed in main operation screen.
Alarm Delay ParameterAfter Power On ( Default = 0)
This parameter defines the delay for the alarm is being active after power on.
It can be adjusted from 0 to 99 minutes.
Programming Mode Acessing Password ( Default = 0)
Password for entering to the programming mode is defined with this parameter.
It can be adjusted from 0 to 9999. ýf it is 0, programming mode is accessed
without entering password.