EN-KO Electronic Control Systems AMF 4.0/ENG/K.K./02
11
AMF 4.0 PARAMETERS
Initial parameter settings are for genset model 10. These are as following table. For chosen
genset model, parameter table can be loaded by means of parameter 69. Parameters that is
changed according to genset models are specified in the next sections.
No Parameter Setting Range Default Value
Operator Parameters
P0 Operator menu password 0-999 050
P1 Temperature unit 0: Celsius
1: Fahrenheit
0
P2 Crank attempts 1 – 9 3
P3 Cranking time 1-60 sec 10 sec
P4 Cranking pause time 3-60 sec 10 sec
P5 Manuel cranking type 0: Start button must be held down to crank
1: Automatic start
0
P6 Preheating type 0:Preheat button must be hold down to preheat
1: Automatic preheat
0
P7 Auxiliary input 1 function 0: Input disabled
1: Yellow alarm (always active)
2: Yellow alarm (active from starting)
3: Yellow alarm (active form engine stabilization time)
4: Red alarm (always active)
5: Red alarm (active from starting)
6: Red alarm (active from engine stabilization time)
7: Remote start
8: Remote main failure disable
9: Mains available
10: Emergency stop
11: Cabinet thermostat alarm
6
P8 Auxiliary input 2 function Same as auxiliary input 1 0
P9 Auxiliary input 3 function Same as auxiliary input 1 10
P10 Auxiliary input 4 function Same as auxiliary input 1 4
P11 Auxiliary input 1 activation method 0: Close to activate
1: Open to activate
0
P12 Auxiliary input 2 activation method Same as auxiliary input 1 0
P13 Auxiliary input 3 activation method Same as auxiliary input 1 0
P14 Auxiliary input 4 activation method Same as auxiliary input 1 0
P15 Auxiliary output 1 function 0: Output disabled
1: Engine running
2: Panel is in auto or test mode
3: Yellow alarm
4: Red alarm
5: Common alarm
6: Horn
7: Panel is in manual, auto or test mode
8: Panel is in auto mode
9: 6 sec stop output during engine stop
10: Fuel solenoid output
11: Auxiliary services
0
P16 Auxiliary output 2 function Same as auxiliary output 1 0
P17 Auxiliary output 3 function Same as auxiliary output 1 0
P18 Auxiliary output 1 activation method 0: De-Energize
1: Energize
1
P19 Auxiliary output 2 activation method Same as auxiliary output 1 1
P20 Auxiliary output 3 activation method Same as auxiliary output 1 1
P21 Test Mode 0: Test off load
1: Test on load
0
P22 Max. Stop solenoid working time 1-180 sec 6 sec