EN-KO Electronic Control Systems AMF 4.0/ENG/K.K./02
15
PARAMETER DESCRIPTIONS
No Parameters Description
Operator Parameters
P0 Operator menu password Operator password can be changed by this parameter
P1 Temperature unit This parameter selects coolant temperature unit shown in the
display. According to selected unit “high coolant
temperature level“ is adjusted.
P2 Crank attempts Number of cranking during starting in automatic, test and
manual modes.
P3 Cranking time Cranking time during automatic cranking
P4 Cranking pause time Interval between two cranking period in automatic and test
modes.
P5 Manuel cranking type If this parameter selected”0”, operator must hold down start
button pressed during cranking period. If this parameter
selected “1” panel will perform cranking for “cranking
time”. Crank is disconnected automatically when panel
detects engine-running signals.
P6 Preheating type If this parameter selected”0”, operator must hold down
preheat button pressed during preheating period. If this
parameter selected “1” panel will perform preheating for
“Preheat time”.
P7 Auxiliary input 1 function It selects function of auxiliary input
Auxiliary input can be adjusted as red or yellow
alarm. Activation time can be “always active, active
from engine starting or active from engine
stabilization time”. When input activates auxiliary
input led lit and A1.A2, A3 or A4 message is shown
according to activated auxiliary input number.
When remote start input is activated generator starts
and generator contactor closes. If input deactivated
generator contactor opens, engine enters cooling
period and then generator stops. Remote start is
active only in automatic mode.
When mains failure disable input is activated if
mains failure occur generator doesn’t start. Generator
opens mains contactor.
If mains available input is activated panel assume
mains is available. If this input deactivated genset
return to its normal mode.
If emergency stop button is pressed, generator opens
generator contactor and stops immediately. Panel
show “StP” message in the display. To clear
emergency stop alarm, emergency stop button must
be pulled back and alarm clear button must be
pressed.
Cabin thermostat function is used in cabinet type