SPECIFICATIONS
Power Supply
9-35 VDC
140 mA (all relays are de-energized)
Ambient
Temperature
-10°C / +70°C
Relative Humidity
%10-%95 non-condensing
Relay outputs
For cranking, fuel solenoid, preheating and auxiliary outputs max.
12V/24VDC 6 A, For mains and generator contactor relays max.
250VAC/10 A
Voltage measurement
20-300VAC
Frequency
measurement
1-99 Hz
Current
measurements
.../5 A current inputs (current transformer should be used)
Connection
Screw socket
Measurement
Accuracy
Phase voltages : + / - %2
Frequency : + / - 0.1Hz
Phase currents : + / - %2
Charge Excitation
Current
80mA @ 12VDC
160mA@ 24VDC
Housing
PPO (Polyphenylene oxide) %30 Glass Fiber
Protection Class
IP 52 (Front side)
Weight
600 gr. (aprox.)
Dimensions (WxHxD)
192x144x62 mm
Panel Cut Out
186x138 mm
Mounting Installation
Front panel mounted with metal screw fixings