EN-KO Electronic Control Systems AMF 4.0/ENG/K.K./02
20
Enter model number to load parameter table of selected
genset model.
P70
Periodic service time This parameters selects After how many running hour
periodic service alarm will be given
P71
Engine hour adjustment Engine hour is adjusted by this parameter.
P72
Clear last ten alarm When you select “YES” and press menu key last ten failure
is cleared.
P73
Clear periodic service alarm When you select “YES” and press menu key, periodic
service alarm is cleared and service time is reset
P74
Return to technician factory
defaults
When you select “YES” and press menu key technician
parameters is returned to factory defaults
Calibration Parameters
P75
Calibration menu password Calibration menu password adjustment
P76
Mains Vr gain Mains line R voltage gain calibration.
P77
Mains Vs gain Mains line S voltage gain calibration.
P78
Mains Vt gain Mains line T voltage gain calibration.
P79
Generator Vr gain Generator line R voltage gain calibration.
P80
Generator Vs gain Generator line S voltage gain calibration.
P81
Generator Vt gain Generator line T voltage gain calibration.
P82
Generator Ir gain Generator line R current gain calibration.
P83
Generator Is gain Generator line S current gain calibration.
P84
Generator It gain Generator line T current gain calibration.
P85
Battery Voltage gain Battery voltage gain calibration.
P86
Mains Vr offset Mains line R voltage offset calibration.
P87
Mains Vs offset Mains line S voltage offset calibration.
P88
Mains Vt offset Mains line T voltage offset calibration.
P89
Generator Vr offset Generator line R voltage offset calibration.
P90
Generator Vs offset Generator line S voltage offset calibration.
P91
Generator Vt offset Generator line T voltage offset calibration.
P92
Battery voltage offset Battery voltage offset calibration.
P93
Oil pressure offset Oil pressure offset calibration.
P94
Temperature offset Coolant temperature offset calibration.
P95
Generator Ir offset Generator line R current offset calibration.
P96
Generator Is offset Generator line S current offset calibration.
P97
Generator It offset Generator line T current offset calibration.
P98
Return to calibration factory
defaults
When you select “YES” and press menu key calibration
parameters is returned to factory defaults
P99
Mains contactor control in off
mode
If this parameter is selected as “YES”, Unit will control
mains voltages in off mode and when mains exceed the
limits defined in parameter menu, mains contactor opens and
protect the load and when mains returns to normal condition
mains contactor closes. If this parameter is selected as “NO”,
mains isn’t controlled and mains contactor is always closed.