EN-KO Electronic Control Systems AMF 4.0/ENG/K.K./02
18
started in auto mode. Mains failure delay is waited before
mains failure.
P38
Generator under voltage failure
If generator voltage fall below this limit under over voltage
alarm occur. Failure occurred after generator voltage failure
delay
P39
Generator over voltage failure If generator voltage exceeds this limit under over voltage
alarm occur. Failure occurred after generator voltage failure
delay
P40
Generator under frequency
failure
If generator frequency fall below this limit under over speed
alarm occur. Failure occurred after generator frequency
failure delay
P41
Generator over frequency
failure
If generator frequency exceeds this limit under over speed
alarm occur. Failure occurred after generator frequency
failure delay
P42
Last 10 failure Last ten alarm is recorded in the panel memory. There alarm
can be controlled by this parameter.
P43
Return to operator factory
defaults
When you select “YES” and press menu key operator
parameters is returned to factory defaults
Technician Parameters
P44
Technician menu password Technician password can be changed by this parameter
P45
Analog oil sender type Analog oil pressure sender type can be selected from this
parameter. If genset has only digital oil switch, and this
parameter is adjusted to “0” oil switch input is transferred to
analog oil pressure sender input.
P46
Oil switch type Oil pressure switch type can be selected from this parameter.
P47
Low oil pressure failure If oil pressure fall below this limit. Oil pressure failure alarm
is activated.
P48
Analog temperature sender
type
Analog coolant temperature sender can be selected from this
parameter. If genset has only digital coolant temperature
switch, and this parameter is adjusted to “0” coolant
temperature switch input is transferred to analog temperature
sender input.
P49
Digital temperature switch type
Analog coolant temperature sender can be selected from this
parameter.
P50
Analog Oil pressure usage If analog sender is used for display purposes only. Generator
doesn’t control this analog value. Value read from sender is
used only for display purposes. No sensor alarm is given if
sensor cable breaks.
P51
Analog temperature sensor
usage
If analog sender is used for display purposes only. Generator
doesn’t control this analog value. Value read from sender is
used only for display purposes. No sensor alarm is given if
sensor cable breaks.
P52
Fueling system Fueling system is can be adjusted as operating or stop
solenoid. When this parameter is selected as ECU type.
Cranking output behaves like start output and fuel solenoid
output behaves like stop output. This configuration is
necessary in some type of ECU managed engines. In engine
starting condition, start output is activated for 3 second and
cranking is stopped by means of activating stop output for 2