3 OPERATION AND TESTING
3-4
Therma-Flow
®
PLUS
IOM 09900002 Revision C 08/15/21
© 2021, Encon Safety Products, Inc.
3.5 Therma-Flow
®
Plus Inspection Report
DATE
AREA
TAG
NUMBER
MODEL
NUMBER
SERIAL
NUMBER
I. VISUAL INSPECTION
UNIT VISIBILITY
ENCLOSURE PROVIDES A MIN. UNOBSTRUCTED AREA OF 34 (86.4 cm) IN DIAMETER
AREA FREE OF DEBRIS (Within 10 seconds from hazard, Out of potential spray path)
AREA LIGHT/ALARM LIGHT/INTERIOR LIGHT
SIGN CONDITION
EYEWASH COVERS ATTACHED AND IN PLACE ON NOZZLES
SHOWER POSITIONED TO PROVIDE FLUID PATTERN HEIGHT AT MIN. 82” MAX. 96” FROM STANDING LEVEL
EYEWASH (Min. 33” Max. 45” from standing level and min. 6” from nearest obstruction)
VALVES (q Leaking: Eyewash Shower Drench Hose)
ACTUATORS EASILY LOCATED AND READILY IDENTIFIABLE
PULL ROD NO GRATER THAN 69” FROM STANDING LEVEL
INSULATION AND COVERS (q Adjustment q Replacement)
HEAT TRACE INDICATOR LIGHT (q On q Off) if applicable
FREEZE / SCALD PROTECTION VALVES (q Leaking: F.P. Valve S.P. Valve)
OK NO
II. OPERATIONAL INSPECTION
SHOWER VOLUME (Min. 20 gpm / 75.7 lpm)
SHOWER PATTERN TEST (20diameter pattern 60” from standing level)
SHOWER VELOCITY, NONINJURIOUS TO USER (q Too High q OK)
EYEWASH VOLUME (Min. 0.4 gpm / 1.5 lpm)
EYEWASH PATTERN TEST
EYEWASH VELOCITY, NONINJURIOUS TO USER (q Too High q OK)
STAY OPEN VALVES “OFF” TO “ON” IN ONE SECOND OR LESS COMPONENTS
OPERATE SIMULTANEOUSLY TO ANSI REQUIRMENTS
ALARM TEST Local: Shower q OK q No; Eyewash q OK q No; Drench Hose q OK q No
Remote: Shower q OK q No; Eyewash q OK q No; Drench Hose q OK q No
SUPPLY WATER PRESSURE (Min. 30 psig / 207 kPag):
WATER TEMPERATURE (78° to 92°F / 25.6° to 33.3°C):
OK NO
Comments:
Corrective
action required to the shower/shower parts to place unit in operational readiness state:
Action required other than to the shower/shower parts to correct operation:
Report sent to: q Maintenance for action q Record keeping