XA01007T iTEMP TMT71, TMT72, TMT82, TMT84, TMT85
14 Endress+Hauser
The remote or integral mounted temperature sensor must comply
with the requirements according to IEC/EN 60079-1.
Use for integral temperature sensors only approved sensors certified
for category 2G marked not less than II2G Ex d IIC T6…T4 Gb for use
in Zone 1.
Use for integral temperature sensors only approved sensors certified
for category 1G or 2G marked not less than II1/2G Ex d IIC T6…T4
Ga/Gb or II2G Ex d IIC T6…T4 Gb for use in Zone 0 resp. Zone 1.
The temperature class specified for the certified temperature sensor
shall be taken into account.
The transmitter must be installed so, that even in the event of rare
incidents, an ignition source due to impact or friction between the
enclosure and iron/steel is excluded.
L
WARNING
Explosive atmosphere
Do not open the electrical connection of the power supply circuit
under voltage in an explosive atmosphere.
Dust ignition protection
Comply with the installation and safety instructions in the Operating
Instructions.
Install the device according to the manufacturer's instructions and
any other valid standards and regulations (e.g. IEC/EN 60079-14).
Seal the cable entries tight with certified cable glands (min. IP6X)
IP6X according to IEC/EN 60529.
The provided cable glands according to option code are suitable
ATEX/IECEx Ex-certified cable glands with a temperature range of
-20 °C...+95 °C.
For operating the transmitter housing at an ambient temperature
under -20 °C, appropriate cables, cable entries and sealing facilities
permitted for this application must be used.
The housing of the field transmitter must be connected to the
potential matching line.
For ambient temperatures higher than +70 °C, use suitable heat-
resisting cables or wires, cable entries and sealing facilities for Ta
+5K above surrounding.
Use for integral temperature sensors only approved sensors certified
for category 1D or 2D marked not less than II1/2D Ex ta/Ex tb IIIC
T135 °C Da/Db or II2D Ex tb IIIC T135 °C Db for use in Zone 21.
The maximum surface temperature specified for the certified
temperature sensor shall be taken into account.
L
WARNING
Explosive atmosphere
Do not open the device when voltage is supplied (ensure that the IP
66/67 housing protection is maintained during operation).