Levelflex FMP51 Modbus
Endress+Hauser 33
Installation in nozzles ≥ DN300
If installation in ≥ 300mm/12" nozzles is unavoidable, installation must be carried out in accordance
with the following sketch.
1
2
3
4
A0014199
1 Lower edge of the nozzle
2 Approx. flush with the lower edge of the nozzle (± 50 mm/2")
3 Plate
4 Pipe  150 to 180 mm (6 to 7 inch)
Nozzle diameter Plate diameter
300 mm (12") 280 mm (11")
≥ 400 mm (16") ≥ 350 mm (14")