Levelflex FMP56, FMP57
52 Endress+Hauser
Non-metallic vessels
1
2
A0012527
1 Non-metallic vessel
2 Metal sheet or metal flange
To measure, Levelflex with a rod probe needs a metallic surface at the process connection. Therefore:
Select an instrument version with metal flange (minimum size DN50/2").
Or: mount a metal sheet with a diameter of at least 200 mm (8") to the probe at the process
connection. Its orientation must be perpendicular to the probe.