EasyManua.ls Logo

Endress+Hauser Levelflex FMP56 - Page 150

Endress+Hauser Levelflex FMP56
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating menu Levelflex FMP56, FMP57 FOUNDATION Fieldbus
150 Endress+Hauser
For "Operating mode" = "Level" and "Medium type" = "Solid"
Process property Step response time / s
Very fast > 100 m (333 ft) /h 37
Fast > 10 m (33 ft) /h 37
Standard < 10 m (33 ft) /h 74
Medium < 1 m (3ft) /h 146
Slow < 0.1 m (0.3ft) /h 290
No filter / test < 1
For "Operating mode" = "Interface" or "Interface with capacitance"
Process property Step response time / s
Very fast > 10 m (400 in)/min 5
Fast > 1 m (40 in)/min 5
Standard < 1 m (40in) /min 23
Medium < 10 cm (4in) /min 47
Slow < 1 cm (0.4in) /min 81
No filter / test 2.2
Advanced process conditions
Navigation  Setup → Advanced setup → Level → Adv. conditions
Description Specify additional process conditions (if required).
Selection None
Oil/Water condensate
Probe near tank bottom
Build up
Foam (>5cm/0,16ft)
Factory setting None
Additional information Meaning of the options
Oil/Water condensate (only Medium type = Liquid)
Makes sure that in the case of two-phase media only the total level is detected (example:
oil/condensate application).
Probe near tank bottom (only for Medium type = Liquid)
Improves the empty detection, especially if the probe is mounted close to the tank
bottom.
Build up
Enables a safe empty-detection even if the end-of-probe signal has shifted due to build-
up.
Foam (>5cm/0,16ft) (only for Medium type = Liquid)
Optimizes the signal evaluation in applications with foam formation.

Table of Contents

Other manuals for Endress+Hauser Levelflex FMP56

Related product manuals