Loading...
Liquiphant M/S with FEL56 and Nivotester FTL325N
Endress+Hauser 15
A0022347-EN
1oo2 architecture (CONF 4)
Liquiphant (FEL56)
Settings 1) Density 0,7 / 0,5
2) MIN safety
Nivotester FTL325N-#3#3
Settings
(Three-channel device)
A0022197
Error current signal
> 2,1 mA
SIL SIL 2
HFT 1
SFF 88%
PFD
av
** 0,0019 x 10
-2
Wiring scheme
A0022198
Recurrent test
e.g. lowering the level
** TI (test interval) = annual
CH2
CH1
CH3
CH1 + CH2
0,0 2,0 4,0 6,0 8,0 10,0
2,50E-04
2,00E-04
1,00E-04
5,00E-05
0,00E+00
1,50E-04
PFD
PFD
avg
Test interval
[years]
1oo2D structure