BA00239F/00/EN/13.12
71164392
Valid as of software version:
V 01.04
Operating Instructions
Prosonic M FMU40/41/42/43/44
Ultrasonic Level Measurement

Table of Contents

Other manuals for Endress+Hauser Prosonic M FMU41

Questions and Answers

  • W
    whiteshannonAug 19, 2025
    What to do if the measured value jumps sporadically on Endress+Hauser Prosonic M FMU41?
    • T
      Thomas HansenAug 20, 2025
      If you observe the measured value jumping sporadically to higher levels with an uneven surface, you can: 1. Perform interference echo suppression. 2. Set the process conditions to 'calm surface' or 'add. agitator'. 3. Increase output damping. 4. If necessary, choose a different installation position or a larger sensor.
  • T
    Tracy GonzalezAug 21, 2025
    What to do if there is no change in measured value on filling/emptying with Endress+Hauser Measuring Instruments?
    • T
      Theresa GoldenAug 21, 2025
      If you notice no change in the measured value during filling or emptying: 1. Perform interference echo suppression. 2. Clean the sensor if needed. 3. If necessary, select a better installation position. 4. If wide interference echoes are present, set the function "detection window" (0A7) to "off".
  • A
    Amy ReillyAug 23, 2025
    What to do if measured value is incorrect but measured distance is correct on Endress+Hauser Measuring Instruments?
    • R
      Rachel AndersonAug 25, 2025
      If the measured value is incorrect, but the measured distance is correct: 1. Check the empty calibration and full calibration. 2. Check linearisation – level/ullage – max. scale – diameter vessel – linearisation table.
  • R
    Richard PetersAug 26, 2025
    How to fix E 641 (echo loss) error on Endress+Hauser Prosonic M FMU41 Measuring Instruments?
    • D
      Donna PattonAug 26, 2025
      To address an E 641 (echo loss) error: 1. Check application parameters. 2. If needed, choose a different installation position or a larger sensor. 3. Align the sensor parallel to the product surface, especially for bulk solids applications.
  • T
    Taylor PorterAug 27, 2025
    How to resolve 'no usable echo' on Endress+Hauser Measuring Instruments?
    • M
      Matthew MayAug 28, 2025
      To solve the 'no usable echo' issue, check the basic calibration.
  • J
    Jennifer CarrollAug 29, 2025
    What to do if a download error occurs on Endress+Hauser Prosonic M FMU41 Measuring Instruments?
    • B
      bushjustinAug 30, 2025
      If you encounter a download error, check the connection and restart the download.
  • M
    Melinda OrtizAug 31, 2025
    What to do if electronics defect is displayed on Endress+Hauser Prosonic M FMU41?
    • D
      Denise ColeSep 1, 2025
      If an electronics defect is indicated, reset the device. Check the system for EMC and improve it if necessary. If the alarm persists after the reset, replace the electronics.
  • N
    nwilsonSep 2, 2025
    How to fix a checksum error on Endress+Hauser Prosonic M FMU41?
    • A
      andrewsgeorgeSep 2, 2025
      To fix a checksum error, perform a reset. If the alarm remains after the reset, replace the electronics.
  • J
    Jennifer NewtonSep 4, 2025
    What to do if 'Sensor type not detected' error appears on Endress+Hauser Prosonic M FMU41 Measuring Instruments?
    • P
      pfischerSep 4, 2025
      If you receive a 'Sensor type not detected' error, exchange the sensor and/or electronics.
  • L
    Lee GreenSep 6, 2025
    What to do if there is an interruption temperature sensor error on Endress+Hauser Measuring Instruments?
    • K
      Kimberly ArnoldSep 6, 2025
      If there is an interruption in the temperature sensor, exchange the sensor.

Summary

Safety instructions

Designated use

Defines the Prosonic M's application and measurement capabilities.

Installation, commissioning, operation

Outlines requirements for safe installation, start-up, and operation.

Operational safety and process safety

Emphasizes safety measures during device configuration, testing, and maintenance.

Notes on safety conventions and symbols

Explains symbols and conventions used to highlight safety-relevant information.

Identification

Nameplate

Details information on the device's nameplate for identification.

Product structure FMU40

Lists configurable options and codes for the FMU40 model.

Product structure FMU41

Lists configurable options and codes for the FMU41 model.

Product structure FMU42

Lists configurable options and codes for the FMU42 model.

Product structure FMU43

Lists configurable options and codes for the FMU43 model.

Product structure FMU44

Lists configurable options and codes for the FMU44 model.

Scope of delivery

Lists the instrument and accessories included in the product package.

Installation

Design; dimensions

Provides physical dimensions and drawings for FMU40/41 and FMU42/44 models.

Installation variants

Illustrates different methods for installing the FMU40 and FMU41 sensors.

Installation conditions

Details environmental and physical conditions for optimal level measurement.

Measuring range

Specifies nozzle diameters, sensor characteristics, and maximum ranges.

Installation hint for FMU40, FMU41

Provides specific guidance for correctly installing FMU40 and FMU41 models.

Post installation check

Lists checks to perform after installation to ensure proper function.

Wiring

Electrical connection

Details procedures and precautions for making electrical connections to the device.

Wiring with FOUNDATION Fieldbus plug

Describes how to connect the device using the FOUNDATION Fieldbus plug.

Supply voltage

Lists minimum and maximum terminal voltages for different device types.

Recommended connection

Provides guidelines for optimal electrical connections, especially for EMC.

Operation

Operation with the display and operating module VU331

Explains how to operate the device using the built-in display and keypad.

On-site operation

Details options for interacting with the device directly at the installation site.

Operation using the on-site display VU331

Provides a step-by-step guide to navigating and operating via the VU331 display.

Remote operation

Explains how to operate the device remotely using configuration tools.

FieldCare operating program

Introduces FieldCare software for device configuration and analysis.

Operation with a FOUNDATION Fieldbus configuration program

Describes configuration using FOUNDATION Fieldbus tools.

Commissioning

Unlocking the device

Explains how to unlock the device to allow parameter changes.

Resetting the device

Describes procedures for resetting device parameters to default or specific states.

Commissioning by the display and operating module VU331

Guides through the initial setup process using the VU331 display.

Commissioning with FOUNDATION Fieldbus configuration tool

Details the steps for commissioning using a FOUNDATION Fieldbus configuration tool.

Troubleshooting

System error messages

Explains how instrument errors are displayed and accessed via different interfaces.

Application errors

Provides guidance on diagnosing and eliminating common application-related errors.

Maintenance and repairs

Repairs to Ex-approved devices

Specifies procedures and personnel qualifications for repairing Ex-approved devices.

Spare Parts

Guides users on how to find and order spare parts via the internet.

Accessories

Weather protection cover

Recommends a weather protection cover for outdoor mounting.

Screw in flange

Lists options for screw-in flanges, including material and sensor connection types.

Remote display FHX40

Presents technical data and mounting options for the FHX40 remote display.

Technical Data

Technical data at a glance

Provides a summary of key technical specifications for the Prosonic M.

Performance characteristics

Details reaction times, operating conditions, value resolution, and measuring errors.

Ambient conditions

Outlines operating temperature, storage, climate class, and ingress protection.

Appendix

Operating menu

Provides a visual map of the device's operating menu structure and function codes.

Block model of the Prosonic M

Explains the different function blocks and their interconnections within the device.

Measuring principle

Explains the ultrasonic time-of-flight method and interference echo suppression.

Endress+Hauser Prosonic M FMU41 Specifications

General IconGeneral
Device TypeUltrasonic Level Measurement
Measurement PrincipleUltrasonic Time-of-Flight
ProtectionIP68
ApplicationLevel measurement of liquids and solids
Measuring Range (Solids)0.3 to 5 m
Process Temperature-40 to +80 °C
Output Signal4...20mA HART
Power Supply24 V DC
Housing MaterialAluminum or Stainless Steel
CommunicationHART
DisplayLCD