Micropilot FMR51, FMR52
28 Endress+Hauser
Supply voltage
An external power supply is required.
Various supply units can be ordered from Endress+Hauser: see "Accessories" section→ 109
2-wire, 4-20mA HART, passive
"Power Supply, Output"
1)
"Approval"
2)
Terminal voltage U at the
device
Maximum load R, depending on the supply voltage U
0
at the
supply unit
A: 2-wire; 4-20mA HART • Non-Ex
• Ex nA
• Ex ic
• CSA GP
10.4 to 35 V
3)
4)
R [ ]?
U
0
[V]
10
10.4 21.4
20 30 35
0
500
A0017140
Ex ia / IS 10.4 to 30 V
3) 4)
• Ex d(ia) / XP
• Ex ic(ia)
• Ex nA(ia)
• Ex ta / DIP
13 to 35 V
5)
U
0
[V]
10
13 24
20 30 35
0
500
R [ ]Ω
A0034771
Ex ia + Ex d(ia) / IS + XP 13 to 30 V
5)
1) Feature 020 of the product structure
2) Feature 010 of the product structure
3) For ambient temperatures T
a
≤ -20 °C (-4 °F) a minimum voltage of 15 V is required for the sartup of the device at the MIN error current (3,6
mA). The startup current can be parametrized. If the device is operated with a fixed current I ≥ 5,5 mA (HART multidrop mode), a voltage of U ≥
10,4 V is sufficient throughout the entire range of ambient temperatures.
4) In the current simulation mode a voltage U ≥ 12.5 V is required.
5) For ambient temperatures T
a
≤ -20 °C (-4 °F) a minimum voltage of 16 V is required for the startup of the device at the MIN error current (3.6
mA).
"Power Supply, Output"
1)
"Approval"
2)
Terminal voltage U
at the device
Maximum load R, depending on the supply voltage U
0
at the
supply unit
B: 2-wire; 4-20 mA HART,
switch output
• Non-Ex
• Ex nA
• Ex nA(ia)
• Ex ic
• Ex ic(ia)
• Ex d(ia) / XP
• Ex ta / DIP
• CSA GP
13 to 35 V
3)
U
0
[V]
10
13 24
20 30 35
0
500
R [ ]Ω
A0034771
• Ex ia / IS
• Ex ia + Ex d(ia) / IS + XP
13 to 30 V
3)
1) Feature 020 of the product structure
2) Feature 010 of the product structure
3) For ambient temperatures T
a
≤ -30 °C (-22 °F) a minimum voltage of 16 V is required for the startup of the device at the MIN error current (3.6
mA).