Micropilot FMR51, FMR52 PROFIBUS PA Electrical connection
Endress+Hauser 33
7.1.3 Supply voltage
PROFIBUS PA, FOUNDATION Fieldbus
"Power supply; Output"
1)
"Approval"
2)
Terminal voltage
E: 2-wire; FOUNDATION Fieldbus, switch output
G: 2-wire; PROFIBUS PA, switch output
Non-Ex
Ex nA
Ex nA(ia)
Ex ic
Ex ic(ia)
Ex d(ia) / XP
Ex ta / DIP
CSA GP
9 to 32 V
3)
Ex ia / IS
Ex ia + Ex d(ia) / IS + XP
9 to 30 V
3)
1) Feature 020 of the product structure
2) Feature 010 of the product structure
3) Input voltages up to 35 V will not spoil the device.
Polarity sensitive No
FISCO/FNICO compliant
according to IEC 60079-27
Yes
7.1.4 Overvoltage protection
If the measuring device is used for level measurement in flammable liquids which requires the
use of overvoltage protection according to DIN EN 60079-14, standard for test procedures
60060-1 (10 kA, pulse 8/20 μs), overvoltage protection has to be ensured by an integrated or
external overvoltage protection module.
Integrated overvoltage protection
An integrated overvoltage protection module is available for 2-wire HART as well as
PROFIBUS PA and FOUNDATION Fieldbus devices.
Product structure: Feature 610 "Accessory mounted", option NA "Overvoltage protection".
Technical data
Resistance per channel 2 * 0.5 Ω max
Threshold DC voltage 400 to 700 V
Threshold impulse voltage < 800 V
Capacitance at 1 MHz < 1.5 pF
Nominal arrest impulse voltage (8/20 μs) 10 kA