Micropilot FMR51, FMR52 FOUNDATION Fieldbus Commissioning (block-based operation)
Endress+Hauser 85
Step Block Parameter Action
8 SETUP (TRDSUP) Distance
(filtered_dist_val)
Displays the distance D between the reference
point R and the level L.
9 SETUP (TRDSUP) Signal quality
(signal_quality)
Displays the signal quality of the level echo.
10 SETUP (TRDSUP) Confirm distance
(confirm_distance)
Compare the displayed distance to the real
distance in order to start the recording of the
mapping curve.
Selection:
• 179: Manual map
• 32847: Factory map
• 32859: Distance ok
• 32860: Distance too big
• 32861: Distance too small
• 32862: Distance unknown
• 33100: Tank empty
1) only available for "Tank type" = "Bypass/pipe"
12.6 Configuration of the on-site display
12.6.1 Factory settings of the on-site display for level measurements
Parameter Factory setting
Format display 1 value, max. size
Value 1 display Level linearized
Value 2 display None
Value 3 display None
Value 4 display None
The on-site display can be adjusted in the DISPLAY (TRDDISP) transducer block.
12.7 Configuration management
After commissioning, you can save the current device configuration, copy it to another
measuring point or restore the previous device configuration. You can do so using the
Configuration management parameter and its options.
Navigation path in the operating menu
Setup → Advanced setup → Conf.backup disp → Config. managem.
Block operation
Block: DISPLAY (TRDDISP)
Parameter: Configuration management (configuration_management)
Functions of the parameter options
Options Description
33097: Execute backup A backup copy of the current device configuration in the HistoROM is saved to the
display module of the device. The backup copy comprises the transmitter data of
the device.
33057: Restore The last backup copy of the device configuration is copied from the display module
to the HistoROM of the device. The backup copy comprises the transmitter data of
the device.