Nivotester FTL325P Design
Endress+Hauser 17
• Minimum level monitoring (dry running protection, MIN detection)
A maximum of one safety function – either MAX detection or MIN detection of a level –
may be performed with a 3-channel Nivotester unit.
A device combination with non-functional safety functions is only possible in accordance
with version VI.
3.3.1 Other safety-related characteristic values
Please note the following in relation to the Declarations of Conformity with safety-related
characteristic values.
A common cause factor β = 10 % has been assumed in the calculations specified.
For multi-channel systems, the PFD
avg
values already contain common cause failures for the
specific wiring scheme.
The PFD
avg
values only apply to the particular wiring scheme for which the values have been
calculated. They are not a suitable basis for making calculations for other wiring schemes.
The use of NC contacts instead of NO contacts, in particular, is not permitted for operation
according to SIL specifications.
The wiring scheme shows the number of devices and the switching of the contacts in the
level relays (contact open in demand mode).
If there are several devices in a wiring scheme, all the devices have the same settings
shown.
The Declarations of Conformity show safety-related values and wiring options for the
measuring system.
FIT = Failure in Time, 1 FIT = 10
-9
1/h
3.3.2 Common cause errors
Where HFT=1, the failure rates are based on an analysis in accordance with
DIN EN 61508-6: 2011-02, Table D.4, "Using the β-factor to calculate the probability of
failure in an E/E/PE safety-related system due to common cause failures".
The calculation gives a β-factor of 10 %.
This factor is based on the failure rates indicated above.
If additional measures are implemented during installation to prevent common cause errors
as defined in Table D.1, the β-factor can possibly be reduced to 5 %.
Possible measures are:
Sensors installed in a physically separate location
Cable routed separately between the Liquiphant and Nivotester
Separate protection from environmental influences:
Impact
Sunshine
EMC protection and/or overvoltage
Use of different sensor materials
Combination of high-temperature and normal version