Commissioning (installation and configuration) Nivotester FTL325P
18 Endress+Hauser
3.4 Basic conditions for use in safety-related applications
The measuring system must be used correctly for the specific application, taking into account
the medium properties and ambient conditions. Carefully follow instructions pertaining to
critical process situations and installation conditions from the Operating Instructions. The
application-specific limits must be observed. The specifications in the Operating Instructions
and the Technical Information must not be exceeded.
3.4.1 EMC compatibility
The Nivotester is certified in accordance with IEC 61326-3-2 and is thus suitable for safety-
related, industrial applications in a specified electromagnetic environment. If the specified
electromagnetic ambient conditions are exceeded, the switch status might not be reliably
detected. An unshielded cable up to 1 000 m (3 281 ft) long can be used between the devices
in these environmental conditions. Electromagnetic interference immunity can be further
improved by using shielded cables.
3.5 Useful lifetime of electric components
The established failure rates of electrical components apply within the useful lifetime as per
IEC 61508-2:2010 section 7.4.9.5 note 3.
According to DIN EN 61508-2:2011 section 7.4.9.5 (national footnote N3) appropriate
measures taken by the operator can extend the useful lifetime.
4 Commissioning (installation and configuration)
4.1 Requirements for personnel
The personnel for installation, commissioning, diagnostics and maintenance must fulfill the
following requirements:
‣
Trained, qualified specialists must have a relevant qualification for this specific function
and task.
‣
Personnel must be authorized by the plant owner/operator.
‣
Be familiar with federal/national regulations.
‣
Before starting work: personnel must read and understand the instructions in the manual
and supplementary documentation as well as the certificates (depending on the
application).
‣
Personnel must follow instructions and comply with general policies.
The operating personnel must fulfill the following requirements:
‣
Personnel are instructed and authorized according to the requirements of the task by the
facility's owner-operator.
‣
Personnel follow the instructions in this manual.
4.2 Installation
The mounting and wiring of the device and the permitted orientations are described in the
Operating Instructions pertaining to the device.