Proof testing Nivotester FTL325P
28 Endress+Hauser
2. Check the status of the safety contacts.
The contacts to be checked must be open.
If one or more safety contacts are closed, a fault has occurred in the safety path. The
proof test has not been passed and must be aborted.
Step 3
1. Release the test button.
Wait for the switching delay to elapse (1 s, unless ordered otherwise).
2. Check the status of the safety contacts.
The contacts to be checked must be closed.
If one or more safety contacts are open, a fault has occurred in the safety path. The proof
test has not been passed and must be aborted.
6.5 Test sequence B, simulation using test button on Nivotester
No change of level in the tank is necessary for this sequence.
Note the following for the test sequences:
Test sequence B (simulation) is not permitted for a commissioning test.
The contacts to be checked depend on the version.
Version II and version VI:
Terminal 4 + 5
Version III:
Terminal 22 + 23
Terminal 26 + 27
Version IV and version V:
Terminal 4 + 5
Terminal 22 + 23
Terminal 26 + 27
Step 1
Check the status of the safety contacts.
The contacts to be checked must be closed.
If one or more safety contacts are open, a fault has occurred in the safety path. The proof
test has not been passed and must be aborted.
Step 2
1. Press the test button and release.
The device restarts (3 s), the status OK (safety contacts closed) is then maintained
for 2 s afterwards.
The demand mode is then maintained for 5 s.