Nivotester FTL325P Commissioning (installation and configuration)
Endress+Hauser 19
4.3 Commissioning
The device is commissioned using the Commissioning Wizard. The commissioning procedure
is described in the Operating Instructions pertaining to the device.
Prior to operating the device in a safety instrumented system, verification must be performed
by carrying out a test sequence as described in Section 6 Proof testing.
4.4 Operation
The operation of the device is described in the Operating Instructions pertaining to the device.
4.5 Device configuration for safety-related applications
The device settings may not be changed if SIL operation is in progress.
NOTICE
The protective function can be impaired
After commissioning the measuring system, changes to the settings can impact the protective
function
After changing the settings, perform a proof test to ensure that the safety function is
working correctly
A
B
A0039550
 1 Explanation of switch settings
A Switch must be configured as shown
B Select the same operating mode as on the electronic insert of the safety function
All channel switches on the Nivotester must be configured to the same operating mode.