Nivotester FTL325P Proof testing
Endress+Hauser 25
6.2 Test sequence A, MIN detection
• Approach the level or
• Remove and immerse in a medium of similar density and viscosity
The contacts to be checked depend on the version.
Version II and version VI:
Terminal 4 + 5
Version III:
• Terminal 22 + 23
• Terminal 26 + 27
Version IV and version V:
• Terminal 4 + 5
• Terminal 22 + 23
• Terminal 26 + 27
Step 1
1. Raise the level or immerse the tuning fork of the sensor that has been removed into the
medium until the tuning fork is fully covered.
If it is not possible to do this with the original medium, a medium of a similar
density and viscosity must be used.
2. Check the status of the safety contacts.
The contacts to be checked must be closed.
If one or more safety contacts are open, a fault has occurred in the safety path. The proof
test has not been passed and must be aborted.
Step 2
1. Lower the level or take the tuning fork of the sensor that has been removed out of the
medium until the tuning fork is completely free.
Wait for the switching delay to elapse (1 s, unless ordered otherwise)
2. Check the status of the safety contacts.
The contacts to be checked must be open.
If one or more safety contacts are closed, a fault has occurred in the safety path. The
proof test has not been passed and must be aborted.
Step 3
1. Re-install the sensor that was removed (optional).
Wait for power-up (10 s).
2. Restore the status OK by fully covering the tuning fork.
Wait for the switching delay to elapse (1 s, unless ordered otherwise).