Commissioning RIA452
30 Endress+Hauser
• Bus error reading the relay data after power-up (E105)
The relay remains picked up even after acknowledging.
• Universal card HW error (E106)
The relay remains picked up even after acknowledging.
• Pulse buffer overflow (E210)
The relay is de-energized after acknowledgement.
• Pump error at the digital input x in question (E22x)
The relay remains picked up even after acknowledging.
Delay
G09-RIA452ZZ-15-00-xx-en-003
Fig. 17: Delay
The following parameters must be configured:
24-hour activation function
Pumps with long downtimes can be activated cyclically with the 24-hour activation function
for the time defined in Sw. period (0-999 seconds).
The starting time for the 24-hour step interval can be postponed by 0 to 23 hours with the
Sw. delay setting.
G09-RIA452ZZ-15-00-xx-en-009
Fig. 18: 24-hour activation function
Example: time at the time of configuration 12 midday, desired start of 24-hour counting
22:00 (10 p.m.) set Sw. delay to 10.
Menu Function (menu item) Setting value
LIMIT 1 to 8/M10 to 17 Setpoint A
Hysteresis
Delay
Value for threshold
Value for hysteresis
Delay time in [s]