RIA452 Commissioning
Endress+Hauser 31
The following parameters must be configured for the example above:
Alternate
G09-RIA452ZZ-15-00-xx-en-007
Fig. 19: Alternating pump control
Alternate switching is used to ensure that several pumps are utilized evenly in level control
systems. The main factor for switching on a certain pump is not a fixed assigned switch-on
value but rather the operating time of the pumps.
In total, the first 4 relays (LIMIT 1 to 4) can be included in the alternating pump control
system.
If power is switched off, the time for the 24-hour activation function starts again.
Menu Function (menu item) Setting value
LIMIT Sw. period
Sw. delay
Activation duration
Activation delay