EasyManuals Logo

ENERGY KINETICS EK2C User Manual

ENERGY KINETICS EK2C
75 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
Accel CS Boiler - Gas Heat - Eighth Edition January, 2015 12
LENGTH OF RUN, INTAKE AND VENT
*Air Inlet and Vent Pipe:
Subtract 5 feet from the maximum length for each
elbow added. A total equivalent length of 50 feet is
allowed. For example, if (5) ninety degree elbows are
used, subtract 5 x 5 ft = 25 feet from the maximum of
50 equivalent feet, for a maximum of 50 ft 25 ft =25
feet of straight pipe allowed.
Fan Speed Set Guide:
Use the following chart to select the optimal fan speed range based on your venting parameters.
Vent
Size
LPG Standard RPMs Alternate RPMs
Natural
Gas
Standard RPMs Alternate RPMs
2”
Venting
EK1C
Low
High
Low
High
EK1C
Low
High
Low
High
15'
1400
6000
1200
4600
15'
1500
6200
1300
4800
25'
1500
6200
1200
4800
25'
1600
6400
1300
5000
50'
1600
6500
1200
5000
50'
1600
6700
1300
5200
3” Venting
EK1C
Low
High
Low
High
EK1C
Low
High
Low
High
15'
1300
5900
1200
5600
15'
1300
6200
1200
5900
25'
1300
6000
1200
5700
25'
1300
6200
1200
5900
50'
1400
6100
1300
5800
50'
1300
6300
1300
6000
75'
1400
6100
1300
5900
75'
1400
6400
1300
6100
100'
1500
6200
1400
6000
100'
1400
6400
1300
6100
EK2C
Low
High
Low
High
EK2C
Low
High
Low
High
15'
1200
5100
1000
4100
15'
1300
5600
1100
4300
25'
1200
5300
1000
4200
25'
1300
5700
1100
4400
50'
1300
5500
1100
4300
50'
1300
5800
1100
4500
75'
1400
5700
1100
4400
75'
1400
5900
1200
4600
100'
1400
5800
1100
4500
100'
1400
6000
1200
4700
EK3C
Low
High
Low
High
EK3C
Low
High
Low
High
15'
1400
6700
1200
5400
15'
1600
7200
1300
5600
25'
1500
7000
1200
5800
25'
1600
7500
1300
5900
50'
1600
7800
1200
6200
50'
1700
7800
1300
6400
Fan Speed Set Guide (Continued)
4” Venting
EK3C
Low
High
Low
High
EK3C
Low
High
Low
High
15'
1500
7100
1200
5400
15'
1500
7300
1200
5600
25'
1500
7100
1200
5400
25'
1500
7400
1200
5700
50'
1500
7200
1200
5500
50'
1600
7600
1200
5800
75'
1600
7200
1200
5500
75'
1600
7800
1300
5900
100'
1600
7300
1300
5600
100'
1600
7800
1300
6000
Model
Inlet & Outlet
Pipe Size
Maximum Length*
EK1C
2”
50 Feet
3”
100 Feet
EK2C
3”
50 Feet
4”
100 Feet
EK3C
3”
50 Feet
4”
100 Feet

Questions and Answers: