5. Operation
Constant voltage chargers are recommended. The charging
voltage should be set at the equivalent of 2.27Vpc at
77°F/25°C or 2.29Vpc at 68°F/20°C. The minimum charging
voltage, at any temperature, is 2.21 volts per cell. The
recommended float voltage temperature compensation is:
Do not over-discharge the battery. This can be avoided by
including a Low Voltage Disconnect switch in the circuit or by
disconnecting the battery from the load when the end
discharge voltage is reached. The float voltage must be
applied to the battery as soon as possible, and not later than
7 days after any discharge.
6. Maintenance
In practice the user usually specifies the maintenance
schedule based on site criticality, location and manpower.
The following is a suggested maintenance schedule.
Every Six Months (Record All Readings)
Measure the battery string voltage. If necessary, adjust the
float voltage to the correct value.
Measure individual bloc voltages. The blocs should be
within 5% of the average.
All readings should be recorded in a format where sudden
deviations and trends are easily identifiable. If necessary
isolate the string/bloc and clean with a damp soft cloth.
Do not use solvents or scouring powders to clean the blocs.
Contact EnerSys
®
if you have any questions regarding
maintenance.
7. Disposal
PowerSafe
®
SBS batteries are recyclable. Scrap batteries
must be packaged and transported in accordance with
prevailing transportation rules and regulations.
Scrap batteries must be disposed of in compliance with
local and national laws by a licensed or certified lead acid
battery recycler.
SBS 8 2205-8982 2205-8981
SBS 15 2205-9851 2205-9850
SBS 30, 40 2204-1123 2204-1124
SBS 60 2204-1123 2205-4260
SBS 110 - 300 2205-9887 2205-8865
SBS 390 2205-9759 x 2 N/A
SBS J13, J16 2205-9851 2205-9850
SBS J30, J40 2204-1123 2205-4260
SBS J70 2204-1123 2205-4420
SBS B8 - 14 N/A 2205-8919
Type
Connector Part No.
A B
Temperature °F / °C
50/10 59/15 68/20 77/25 86/30 95/35 104/40
Recommended 2.33 2.31 2.29 2.27 2.25 2.23 2.21
Minimum 2.31 2.29 2.27 2.25 2.23 2.21 2.21
Type
Connector Part No.
A B
SBS C11 N/A 2205-8919
SBS 145, 145F-V 2205-0163 2205-0163
SBS B8F-14F C11CONN N/A
SBS C11F C11CONN N/A
SBS 145F 2205-0162 N/A
SBS 170F-190F VFCONN N/A
SBS 100 N/A 907054
SBS 100F 907052 N/A
SBS 112F VFCONN N/A
SBS 110 - 300 SBS 390 SBS 110 - 300
B A A
B
SBS B8 - 14, C11, 100, 145
Top Terminal
SBS B8 - 14, C11, 170F, 190F,
100F, 112F
Front Terminal
A
SBS J30, J40
A
SBS J30, J40
B
B B
B
SBS 8-60, J13, J16, J70
SBS 8-60, J13, J16, J70
A
A
EnerSys de Mexico
S.A. de C.V.
Ave. Presidente Juarez 74-A
Col. Bellavista C.P. 54080
Tlalnepantam Estado
de Mexico
Tel: (52-55)-2628-0504
Fax: (52-55)-5362-7774
EnerSys
2366 Bernville Road
Reading, PA 19605
USA
Tel: +1-610-208-1991
+1-800-538-3627
Fax: +1-610-372-8613
EnerSys
444 Foxon Rd
East Haven, CT 06513
Tel: (203)-469-0070
Fax: (203)-773-1010
Sales and Support Locations
EnerSys
61 Parr Blvd
Bolton, Ontario
Canada L7E 2Z8
Tel: (905)-951-4441

Other manuals for EnerSys PowerSafe SBS

Related product manuals