7.2 Regulations Covering Insert Installation
When installed and operated as described in these instructions, the Solution 1.8 wood insert is
suitable for use in residential installations. The Solution 1.8 wood insert is not intended for
installation in a bedroom.
In Canada, the CSA B365 Installation Code for Solid Fuel Burning Appliances and Equipment
and
the CSA C22.1 Canadian National Electrical Code
are to be followed in the absence of local code
requirements. In the USA, the ANSI NFPA 211 Standard for Chimneys, Fireplaces, Vents and
Solid Fuel-Burning Appliances and the ANSI NFPA 70 National Electrical Code are to be followed
in the absence of local code requirements.
This insert must be installed with a continuous chimney liner of 6” diameter extending from the
insert to the top of the chimney. The chimney liner must conform to the Class 3 requirements of
CAN/ULC-S635, Standard for Lining Systems for Existing Masonry or Factory-built Chimneys and
Vents, or CAN/ULC-S640, Standard for Lining Systems for New Masonry Chimneys or UL1777,
Standard for Safety for Chimney Liners.
NOTE: The Insert is not approved for use with a so-called “positive flue connection” to the clay
tile of a masonry chimney.