IOM-17 26 of 27 Mar 99 R3
HEATOPERATIONFLOWCHART
MainSupplypower‘ON’
ServiceSwitch‘ON’
Firealarmcontact‘CLOSED’
24VaconT1,T2
24VaconFS,HS
Heatcall
light’ON’?
PPlight
’ON’?
Heatcall
light’2SEC
FLASH’?
Noheatcall
Restore24Vac
to‘HS’
Anylights
Flashing?
Indicates
possible
lockout
10Vdcon
terminals
O
or
G
?
Combustion
fanstarted?
Pre‐Purge
light‘2SEC
FLASH’?
FaultyDJM3
Faultycombustionfan
Nooutputfromterminal
’CB’
SpeedSensor
Problem
Combustionfan
runningwith5
Vdcacross
terminals‘YS’and
DJM3fuse
failureorfaulty
DJM3
Turnover
magnetor
replace
If0or10Vdcacross‘YS’and‘G’
withCombustionfanrunning,
replacespeedsensor
Ignition
Enablelight
Unitstuckin
Pre‐Purge
PowergoestoIgnition
Control,burnerwill
light.OnceDJM3
receivesfeedbacksignal,
firingratewillmodulate.
Normalo
p
eration
YES
YES
YES
NO
NO
NO
YES
YES
NO
NO
YES
YES
YES
NO
NO
NO
YES
NO