IOM-12 Page 1 March 1999 R1
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
FOR
C-TRAC2
COOLING CONTROLLER
UNIT MODEL NO. _________________
UNIT SERIAL NO. _________________
SERVICED BY: ___________________
TEL. NO: ________________________
CANADIAN
HEAD OFFICE
AND FACTORY
USA
HEAD OFFICE
AND FACTORY
CANADIAN
EASTERN FACTORY
1401 HASTINGS CRES.
SE
CALGARY, ALBERTA
T2G 4C8
Ph: (403) 287-4774
Fx: 888-364-2727
32050 W. 83
rd
STREET
DESOTO, KANSAS
66018
Ph: (913) 583-3181
Fx: (913) 583-1406
1175 TWINNEY DRIVE
NEWMARKET,
ONTARIO
L3Y 5V7
Ph: (905) 898-1114
Fx: (905) 898-7244
SALES OFFICES ACROSS CANADA AND USA
Retain instructions with unit and maintain in a legible condition.
Please give model number and serial number when contacting
Engineered Air for information and/or parts.
www.engineeredair.com

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the EngA C-TRAC2 and is the answer not in the manual?

EngA C-TRAC2 Specifications

General IconGeneral
BrandEngA
ModelC-TRAC2
CategoryController
LanguageEnglish

Summary

VII. DIP SWITCHES AND POTS

VIII. POTS AND DIP SWITCH CHART

XIV. SENSORS AND SET-POINTS

The Master Set-Points

Primary set points for economizer and mechanical cooling.

XI. CONTROL START-UP AND OPERATING STRATEGIES

Economizer Control

Configuration and operation of economizer functions.

Cooling

Details on compressor ambient lockout and cooling delays.

XVII. ROOM RESET THERMOSTAT OPTIONS

XX. SET-POINT CALIBRATION

Discharge Temperature Calibration Methods

Methods for calibrating discharge temperature.

Discharge Calibration Method 1

Procedure for calibrating discharge temperature.

Discharge Calibration Method 2

Discharge Calibration Method 3

Discharge Calibration Method 4

Room or Return Air Temperature Calibration Methods

Room Calibration Method 1

Room Calibration Method 2

Ambient Reset Calibration

XXI. C-TRAC2.1 SET UP SHEET

XXII. TROUBLE SHOOTING

To Simulate a Full Call for Cooling

Procedure to simulate a cooling demand.

To Simulate a Full Call for Heat

Procedure to simulate a heating demand.

Heating Trouble Shooting

Overheating

Troubleshooting causes and solutions for overheating.

No Heat

Discharge Too Cool

Hunting (External Causes)

Possible C-TRAC2.1 Adjustments to Reduce Hunting

Economizer Trouble Shooting

0 to 10 VDC Motors

Troubleshooting 0-10 VDC economizer motors.

Motors wired to R, B, and W terminals

Troubleshooting R, B, W wired economizer motors.

Economizer Not Opening

Mechanical Cooling Trouble Shooting

Cooling Not Running

Steps to take when mechanical cooling is not running.

QUICK CHECK FOR C-TRAC-2.1 NORMAL OPERATING SEQUENCE

AIR CONDITIONING (Air Cooled Condenser)

Determine type of compressor - Hermetic (welded) or Semi-Hermetic (bolted)

If compressor doesnt run:

Troubleshooting steps when a compressor fails to run.