A G-TRAC2
IOM-25 21 of 42 Mar 99 R7
Calculated Discharge Table for Room and Ambient Reset
ROOM RESET
AMBIENT RESET
Max. Discharge
Temp. (when
room calls for
heat)
Min. Discharge
Temp. (when
room is too
warm)
Max. Discharge
Temp. (when
ambient is <15ºC)
Min. Discharge
Temp. (when
ambient is >70ºF)
Total
Band
Width
Discharge
Set-Point
Pot 5
Setting
ºC
ºF
ºC
ºF
ºC
ºF
ºC
ºF
15.5ºC
60ºF
1
22.5
72.5
12.5
54.5
21.5
70.5
13
55
15.5
2
24
75
12
53.5
3
25.5
78
11.5
53
23.5
74.5
12
53.5
21
4
28.5
83.5
10.5
51
5
35.5
96
9
48
26
79
11
52
27
21ºC
70ºF
1
28
82.5
17
62.5
26.5
79.5
18
64.5
15
2
29.5
85
16
61
3
31
88
15
59
28
82.5
16.5
62
20.5
4
34
93
13
55.5
5
41
106
9
48
29
84.5
15.5
59.5
25
30ºC
86ºF
1
35
95
24
75
34
93
26
78.5
14.5
2
36
97
22.5
72.5
3
37
98.5
21
71
35
95
23.5
74.5
20.5
4
39.5
103
17.5
63.5
5
44
111
13.5
56
37
99
21.5
71
28
NOTE: These are maximum resets. The above table is not linear. There is more reset up from the set point than
down from the set point also. Refer to the explanation on “OR” and “V” and/or "X" and "Z" terminals for
reset information on make/break thermostats.