Rear Panel
Terminal Connections
The positive terminal of the battery must be connected. The value of the terminal must be
between 9 – 30V.
The negative terminal of the battery must be connected. The negative terminal of the battery
should be grounded.
The dry contact output, which controls the Mains contactor. This output is Normally Open.
(250Vac 10A)
The common input of Terminals No 3 and No 5 (MCB). (250Vac 10A)
Caution: In order to enable the related Terminals to COM 1, this input must NOT
be left empty.
The dry contact output, which controls the Mains contactor. This output is Normally Closed.
(250Vac 10A)
The dry contact output, which controls the Generator contactor. This output is Normally Open.
(250Vac 10A)
The common input of Terminals No 6 and No 8 (GCB). (250Vac 10A)
Caution: In order to enable the related Terminals to COM 2, this input must NOT
be left empty.
The dry contact output, which controls the Generator contactor. This output is Normally
Closed. (250Vac 10A)
Functional output. Please refer to parameters P254-P255. (250Vac 6A)
Functional output. Please refer to parameters P256-P257. (250Vac 6A)
Functional output. Please refer to parameters P258-P259. (250Vac 6A)
The common output for Terminals No 9, No 10 and No 11.
Caution: In order to enable the related Terminals to COM 3, this input must NOT
be left empty.
Terminal connection is empty, please do not make any connections.
Terminal connection is empty, please do not make any connections.
Terminal connection is empty, please do not make any connections.
To be connected to Generator chassis for the measurement inputs.