IQ8MC, IQ8AC, IQ8HC, and IQ8X Microinverters Installation and Operation Manual
37 © 2023 Enphase Energy Inc. All rights reserved. November 2023
USM-00008-2.0
Maximum microinverters per 20 A
(maximum) AC branch circuit
3
240 VAC
208 VAC
10
9
Total harmonic distortion
%
<5
Overvoltage class AC port III
AC port backfeed current mA 18
Power factor setting 1.0
Grid-tied power factor (adjustable) 0.85 leading 0.85 lagging
Peak efficiency
240 VAC
208 VAC
%
97.3
97.0
CEC weighted efficiency
240 VAC
208 VAC
%
96.5
96.5
Nighttime power consumption
240 VAC
208 VAC
mW
26
12
Features and specifications
Ambient temperature range -40°C to 65°C (-40°F to 149°F)
Relative humidity range 4% to 100% (condensing)
DC connector type Stäubli MC4
Dimensions (H × W × D) 212 mm (8.3") × 175 mm (6.9") × 30.2 mm (1.2")
Weight
1.1 kg (2.42 lbs)
Cooling Natural convection - no fans
Approved for wet locations Yes
Pollution degree PD3
Enclosure
Class II double-insulated, corrosion-resistant
polymeric enclosure
Compliance
Compliance
CA Rule 21 (UL 1741-SA), UL 62109-1, IEEE1547:2018 (UL
1741-SB), FCC Part 15 Class B, ICES-0003 Class B,
CAN/CSA-C22.2 NO. 107.1-01
This product is UL Listed as PV Rapid Shutdown
Equipment and conforms with NEC 2014, NEC 2017,
NEC 2020, and NEC 2023 section 690.12 and C22.1-
2018 Rule 64-218 Rapid Shutdown of PV Systems for
AC and DC conductors when installed according to
manufacturer's instructions.
1. No enforced DC/AC ratio.
2. The nominal voltage range can be extended beyond nominal if required by the utility.
3. Limits may vary. Refer to local requirements to define the number of microinverters per branch in your area.
4. IQ8X is not certified for use with Enphase Three Phase Network Protection Relay (NPR-3P-208-NA) and, therefore, designed for
single-phase operation only. Check with the local utility requirements to install a single-phase inverter across three phases.