Page 53
710254B
08/7,3/(6&+('8/(23(5$7,21
3C/3C (TRIPLE count/TRIPLE current) can be accomplished on the EN1000. EXTENDED
FUNCTION [SS] must be set to INTERNAL mode. A switch closure between TS1-FS3 and
TS1-GND then will initiate SCHEDULE 00. A switch closure between TS1-FS7 and
TS1-GND will initiate SCHEDULE 10. A switch closure between TS1-FS11 and TS1-GND
will initiate SCHEDULE 20.
SCHEDULE numbers can be externally selected with use of the EXTENDED FUNCTION
SS. In this mode, TS1-FS7/SS1 and TS1-FS11/SS3 become binary schedule selects, and can
point to one of 4 schedules 0,10,20,30. The control is then initiated via TS1-FS3 for any one
of the 4 schedules. See drawing and table below.
SCHEDULE SELECTS VS SCHEDULES
SS1
SS3
SCHEDULE
OPEN
OPEN
0
CLOSED
OPEN
10
OPEN
CLOSED
20
CLOSED
CLOSED
30
For the control to operate in the EXTERNAL SCHEDULE SELECT MODE the control
must be Programmed via use of the EXTENDED FUNCTIONS. The control is factory
configured for TRIPLE SCHEDULE OPERATION. See 3C/3C, above, and section 7.5.