11
Notes:
1The default battery type is Sealed. For Gel, Sealed, Flooded
battery type, the voltage point is fixed, unable to modify it.
2User type is the user defined battery type. The default value is
the same as sealed type. When modify it, please follow the below
logistic relation:
a ) Over Voltage Disconnect VoltageCharging Limit Voltage
Equalize Charging Voltage Boost Charging VoltageFloat
Charging Voltage Boost Reconnect Charging Voltage;
b ) Over Voltage Disconnect VoltageOver Voltage Reconnect
Voltage ;
c) Low Voltage Reconnect VoltageLow Voltage Disconnect Voltage
Discharging Limit Voltage;
d ) Under Voltage Warning Reconnect VoltageUnder Voltage
Warning VoltageDischarging Limit Voltage;
e ) Boost Reconnect Charging voltageLow Voltage Disconnect
Voltage.
*Please carefully to select battery type. It will damage battery if
the setting is incorrect.