Installation
2.34
MASEP/
1
SLAVE
TBl
Figure
2-18.
RMOD
Inter
Module
Wiring
RMOD
WIRING
Referto
Figure2-17,and
Fixture2-18.
1.
Wirethe
inter-RMOD
connections
withina
master/'Slave
RMOD
module
_•roup
servinka
related
hazard(
i.e.
roomand
under
floor).
The
Master/Slave
connectionsare
madetoTB1per
Figure2-18.
2.
Connectthe
RMOD
Field
wiring:
TB2-1
(+),
TB2-2
(-)
Pressure
Supervisory
Circuit.
N.O.Dry
contact
u.sedto
monitor
extinguishing
agent
level.2.0 KB
series
resistor
requiredin
series
with
switch.6.8Kf2 EOL
resistor
required.
TB2-3
(+),
TB2-4
(-)
Manual
Discharg•e
Initialin_Dev iceCircuit.2.0 KB
resistor
requiredin
series
with
contact.6.8 Kf2 EOL res
istor
required.
TB2-5
(+),
TB2-6
(-)
Abort
Initiatin_•
Circuit.2.0 Kf2
resistor
requiredin
series
with
contact.
6.8KB EOL res
istor
required.
When
usedinthe
master/slave
configuration,the
abort
initiatine
circuit
mustbe
wiredtothe
master
RMOD
module.
TB2-7
(+),
TB2-8
(-)
InitiatingDev ice
Circuitf1.
StyleB -3.9Kf2 EOL
required.
StyleC -3.9Kf2 EOL
required.
TB2-9
(+),
TB2-10
(-)
Initiating
Device
CircuitT2.
StyleB -3.9KB EOL required.
StyleC
- 3.9 Kf2 EOL
required.
TB3-1
(+),
TB3-2
(-)
Agent
Release
Solenoid
Circuit#l.
Maximum
solenoid
coil
resistance
ioKn