System
Installation
Note:
flax
imum
current
limits.1 A
iOt9l
both
circuits
svhen in
continuous
mode,2A
total
bothc
ircuils
w'hen
in1
second
pulse
mode.
TB3-3
(+),
TB3-4
(-)
Agent
ReleaseSolenoid
CircuitU.
Maximum
solenoid
coil
resistance
2.0KB.
i'4ote-
Maximum
current
limits.1 A
total
both
circuits
whenin
continuous
mode,2A
total
both
circuits
v•'hen
in1
second
pulse
mode.
TB3-3
(+),
TB3-6
(-)
Discharge
Warning°
Indicatin_•
Appliance
Circuit.15 KB EOL
resistor
required.
When
used
in the
master.*slave
confi
«uration,the
discharge
warning
indicating
appliance
circuit
mustbe
wiredtothe
slave
RMOD
module.
TB3-7
(Normally
Closed),
TB3-8
(Common),TB3-9
(Normally
Open)
alarm
relay.
When
usedinthe
master/slave
configuration,
alarm
relay
wirine
mustbe
connectedtothe
slave
RMOD
module.
TB3-10
(formally
Closed).TB3-1l
(Common).
TB3-12
(Normally
Open)
Pre-Dischar_•e
Relay.
When
used
in the
master'sla›'econfi_•uration,pre
discharge
relay
wiring
mustbe
connectedtothe
slave
RMOD
module.
Inthe
mastersslave
confip•uration:
The
discharge
wamine
notification
appliance
circuitw
iring
mustbe
connectedtothe
slav'e
RMOD.
The
abort
switch
mustbe
wiredtothe
master
RMOD.
RMOD
Configuration
Switches
SW4-I
through
SW4-8set
determinethe
RMOD
configuration.
LSS4
Installation,
Operation,and
Maintenance
Manual
2.35

Related product manuals